CONFIGURING THE METER

Refer to Table 6-1 for a summary list of menu configuration.

SELECTING THE INPUT TYPE ("INPT")
To select your appropriate input type signal, follow these steps:

Note: Before proceeding, Set the input DIP switch settings at the rear of your meter before proceeding. (Refer to Table 2-3).

1. Press the MENU button. The meter shows "INPT".

2. Press the /TARE button. The meter flashes one of the following:
* 0-20 (for 4-20 mA dc) (default)
* 100m (for 0-100 mV dc)
* ▒50m (for ▒50 mV dc)
* 10 V (for 0-10 V dc)
* ▒5 V (for ▒5 V dc)

3. Press the /MAX button to scroll through available choices.

4. Press the MENU button to store your selection. The meter momentarily shows "STRD", followed by "DEC.P" (Decimal Point).


SELECTING A DECIMAL POINT POSITION ("DEC.P")
To select a decimal point display position.

1. Press the MENU button until the meter shows "DEC.P"

2. Press the /TARE button. The meter shows one of the following:
    * FFFF. (default)
    * FFF.F
    * FF.FF
    * F.FFF
3. Press the /MAX button to scroll between available choices.

4. Press the MENU button to store your selection. The meter momentarily shows "STRD", followed by the next menu "RD.S.O" (Reading Scale and Offset). Or you can press the RESET button to abort and go back to the "DEC.P" menu.

SELECTING READING SCALE AND OFFSET (RD.S.0)
Refer to Table 6-1 for a summary list of menu configuration.
To scale the meter to show readings in engineering units. There are two meth-ods. One method is to scale with known inputs. Another method is to scale without known inputs: you calculate input values based on the transducer spec-ifications and manually enter them through the keyboard.

Scaling with Known Loads (On-Line Calibration)
For maximum resolution, find the maximum signal that will be applied to the meter input.
    * For regular voltage input, refer to the main body of Table 4-1 on the following page.
    * For millivolt or milliamp input, refer to the main body of Table 4-2 on the following page.
Set the DIP switch positions as indicated at the top of either Table 4-1 or 4-2. The numbers 1 through 8 in the top row of either table represent DIP switches 1 through 8 and the O, C or X directly below the number indicates the correct position of each switch.
    * "O" Switch should be open or up.
    * "C" Switch should be closed or down.
    * "X" Switch is used to control excitation (refer to Table 2-3 to determine correct position of these switches)
Once DIP switches have been positioned correctly, apply power. Proceed to the "RD.CF" (Reading Configuration) and set R2 equal to the value in the right hand column of the chart.

Range Selection Dip Switch Positions For Regular Voltage Input Table 4-1
12345678
12345678
RD.CF*
XCOOOXXC
XCOOCXXC
R2=
0 - 10 V
▒5 V
4
0 - 5 V
▒5 V
3
0 - 3 V
▒3 V
2
0 - 2 V
▒2 V
1
0 - 1 V
▒1 V
0

Range Selection Dip Switch Positions For Millivolt and Milliamp Input Table 4-2
12345678
12345678
12345678
RD.CF*
XOCOOXXO
XOCOCXXO
XOCCOXXO
R2=
0 - 100 mV
▒50 mV
0 - 20 mA
4
0 - 50 mV
▒50 mV
0 - 10 mA
3
0 - 30 mV
▒30 mV
0 - 6 mA
2
0 - 20 mV
▒20 mV
0 - 4 mA
1
0 - 10 mV
▒10 mV
0 - 2 mA
0
* Reading Configuration

To scale with known inputs: apply known loads to a transducer connected to a meter, or simulate the transducer output with a voltage or current simulator. To scale with known inputs, follow these steps:

1. Apply a known load equal to approximately 0% of the transducer range.

2. Press the MENU button until the meter shows "RD.S.O".

3. Press the /TARE button. The meter shows "IN 1" (Input 1).
Note: "IN 1" (Input 1) is the unscaled display reading at minimum input.

4. Press the /TARE button again. The meter shows the last stored value for Input 1.

5. Press the /TARE button once more. The meter shows the actual signal being received.

6. Press the MENU button to store this value as "IN 1". The meter shows "RD 1" (Read 1).

7. Press the /TARE button. The meter shows the last stored value for Read 1.

8. Press the MAX button to change the value of your digits.

9. Press the /TARE button to scroll horizontally to the next digit.

10.
Press the MENU button to store this value as "RD 1" (Read 1). The meter shows "IN 2" (Input 2).
Note: "IN 2" (Input 2) is the unscaled display reading at maximum input.

11. Apply a known load equal to approximately 100% of the transducer range.

12. Press the /TARE button. The meter shows the last stored value for Input 2.

13. Press the /TARE button once more. The meter shows the actual signal being received.

14. Press the MENU button to store Input 2 value. The meter shows "RD 2" (Read 2).
Note: "RD 2" (Read 2) is the desired display reading at Input 2.

15. Press the /TARE button. The meter shows the last stored value for Read 2.

16. Press the MAX button to change the value of your digits.

17. Press the /TARE button to scroll horizontally to the next digit.

18. Press the MENU button to store this value as "RD 2" (Read 2). The meter momentarily shows "STRD", followed by "RD.CF". Meter scaling is now complete.

Scaling without Known Loads
To scale without known inputs, calculate input values based on the transducer specifications and manually enter them on the keyboard. The following example assumes a pressure transducer with these specifications:

Pressure Range: 0 to 2000 PSI
Output Span: 1 to 5 Vdc

1. Determine the correct values for "IN 1" and "IN 2" based on the transducer specifications. In most cases, "RD 1 & 2" are equal to the minimum and maximum of the transducer output span. The example assumes "RD 1 & 2" are equal to the pressure range of the transducer ("RD 1" = 0000 and "RD 2" = 2000). Calculate "IN 1" and "IN 2" using the transducer output span and the following equation:

"IN" = (Sensor Output) x (Natural Gain) x (Multiplier)

Natural Gain Table 4-3
Input Range
Span Units
Natural Gain
0 to 100 mV
Millivolts
100 cts/mV
+/- 50 mV
Millivolts
40 cts/mV
0 to 10 V
Volts
1000 cts/V
+/- 5 V
Volts
400 cts/V
0 to 20 mA
Millivolts
500 cts/mA

2. Determine the multiplier by the Input Resolution setting ("R.2" in the "RD.CF" menu) and the input range selected. Typically "R.2=4" is suitable for most applications.

Input Resolution Multiplier Table 4-4
Input Range
R.2=4
R.2=3
R.2=2
R.2=1
R.2=0
0 to 100 mV
1.000
2.000
3.333
5.000
10.00
0 to 10 V
1.000
2.000
3.333
5.000
10.00
0 to 20 mA
1.000
2.000
3.333
5.000
10.00
+/- 50 mV
1.000
1.000
1.667
2.500
5.000
+/- 5 V
1.000
1.000
1.667
2.500
5.000

3. Determine "IN 1 & 2" input range and resolution. The example selects the 0 to 100 mV range and 10 uV resolution ("R.2=4").

Example: "IN 1" = (1 Volt) x (1000 cts/v) x (1.000) = 1000
  "IN 2" = (5 Volt) x (1000 cts/v) x (1.000) = 5000
  "RD 1" = 0000
  "RD 2" = 2000

4. Press MENU button until the meter shows "RD.S.O".

5. Press the /TARE button. The meter shows "IN 1" .

6. Press the /TARE button again. The meter shows the last Input 1 value, with the fourth digit flashing.

7. Press the MAX button to change the value of your digits.

8.
Press the /TARE button to scroll horizontally to the next digit.

9. Press the MENU button to store this value. The meter shows "RD 1".

10. Press the /TARE button. The meter shows the last value for Read 1.

Repeat steps 7, 8 and 9 until "RD 1", "IN 2" and "RD 2" have been displayed, verified, changed (if necessary) and stored.

USING READING CONFIGURATION ("RD.CF")
Refer to Table 6-1 for a summary list of menu configuration.
You may use Reading Configuration ("RD.CF") to configure your meter for the following:
    * To enable or disable the front panel tare
    * To set the input resolution of your meter
    * To display the filtered/unfiltered signal input value
Enabling or Disabling the Front-Panel Tare
To enable or disable the front-panel tare, follow these steps:
1. Press the MENU button until "RD.CF" displays.

2. Press the /TARE button. The meter shows one of the following:
* "R.1=T" (Tare enabled) (Default)
* "R.1=N" (Tare disabled)

3. Press the /MAX button to view last stored selection. Press the /MAX button to toggle between selections.

4. Press the /TARE button to select input resolution or press the MENU button to store your selection and enter "S1.CF" (Setpoint 1 Configuration)

Setting the Input Resolution of Your Meter
To set the input resolution of your meter.

1. Press the "MENU" button until "RD.CF" displays, then press the /TARE button twice or Press the /TARE button from "R.1".

One of the following displays (default is "R.2=4"):
    * "R.2=4" 10 ╡V for Unipolar inputs. 25 ╡V for Bipolar inputs.
    * "R.2=0" 1 ╡V for Unipolar inputs. 5╡V for Bipolar inputs.
    * "R.2=1" 2 ╡V for Unipolar inputs. 10╡V for Bipolar inputs.
    * "R.2=2" 3 ╡V for Unipolar inputs. 15╡V for Bipolar inputs.
    * "R.2=3" 5 ╡V for Unipolar inputs. 25╡V for Bipolar inputs.
Example: 3 ╡V resolution means that if you input 0-30 mV, at 30 mV the meter shows 9999.

2. Press the MAX button to scroll through available selections.

3. Press the /TARE button to show the filtered/unfiltered value or press the MENU button to store your selection and enter "S1.CF" (Setpoint 1 Configuration).

DISPLAYING THE FILTERED/UNFILTERED INPUT SIGNAL
To display the filtered/unfiltered signal input, follow these steps:

1. Press the "MENU" button until "RD.CF" displays, then press the /TARE button three times.
or Press the /TARE button from "R.2".

One of the following displays:
* "R.3=F" (Filtered value) (default)
* "R.3=U" (Unfiltered value)

2. Press the /MAX button to toggle between available choices.

3. Press the MENU button to store your selections. "STRD" momentarily displays, followed by "S1.CF" (Setpoint 1 Configuration).
Help Price List Specifications Print Manual Manuals Home
 Home Home
 Table of Contents TOC  Back Back  Next Next